FSL-B-ZAB-SEK_img_17psd.png
FSL-B-ZAB/SEK

00060056_0tif.tif.link

Cross flow heat recovery unit

Energielabel_FSL-B-ZABSEK_150psd.png

Energy label

00073144_0ai.ai.link
Tested to VDI 6022

Tested to VDI 6022

FSL-B-ZAB-SEK_img_16psd.png
Inspection access panel for G3/F7 filter and heat recovery

Inspection access panel for filter and heat recovery unit

 

 

FSL-B-ZAB-SEK_img_15psd.png
Water connection

Water connection

 

 

FSL-B-ZAB-SEK_img_17psd.png
00060056_0tif.tif.link
Energielabel_FSL-B-ZABSEK_150psd.png
00073144_0ai.ai.link
FSL-B-ZAB-SEK_img_16psd.png
FSL-B-ZAB-SEK_img_15psd.png

X-CUBE ROOMAIR-B-ZAB/SEK

Supply and extract air unit with heat exchanger and heat recovery unit, secondary air option, for installation under the sill

Ready-to-operate decentralised ventilation unit that provides good comfort levels, used for the ventilation of internal spaces

  • Acoustically optimised EC fans with low specific fan power, SFP = 0 to EN 16798-3
  • Cross flow heat recovery unit (heat recovery efficiency 60 %)
  • Highly efficient heat exchanger for heating and cooling as 2-pipe or 4-pipe system
  • Heat exchanger connection is on the right when seen from the room
  • Condensate drip tray with condensate drain (on the right when seen from the room)
  • Heat recovery all year round (condensate drainage by others)
  • Reduced fine dust and pollen contamination due to integral filters that conform to VDI 6022 – filter class ISO ePM1 65 % / ISO coarse 85 %
  • Inspection access panel simplifies filter change and cleaning of the heat exchanger
  • Motorised shut-off dampers, normally closed (NC)
  • Automatic switching to secondary air mode (based on air quality)

Optional equipment and accessories

  • Modular control system FSL-CONTROL III, specially for decentralised ventilation systems
  • Various fixing systems to fix the unit to the floor or wall
  • Wood panelling as outer casing in various colours, with TROX ventilation grilles for supply air and extract air (assembly kit)

Műszaki információk

  • FUNCTION
  • TECHNICAL DATA
  • ORDER CODE

Decentralised supply and extract air units ensure room ventilation. They dissipate the cooling loads and heat loads in accordance with the technical data. An EC centrifugal fan takes in the outdoor air and this then flows through the maintenancefree and mechanical self-powered type VFL volume flow limiter, which is pre-set at the factory to the maximum volume flow rate. This ensures maximum limitation of the outdoor air flow rate to a pre-set value for all façade positive pressure situations without an electrical external power supply. The air then flows through the motorised shut-off damper, the self-powered non-return damper and the outdoor air filter. The self-powered non-return dampers in the outdoor air intake and exhaust air outlet prevent the return flow of the conditioned air or undesired airflow directions. Once the outdoor air has passed the fan, it flows through the heat recovery unit; it is possible to bypass the heat exchanger in order to protect it, or when it is sensible with regar to energy efficiency. If necessary, the air is heated or cooled by the heat exchanger before it is discharged to the room as a displacement flow. The extract air first passes through the outdoor air filter, then flows through the heat recovery unit, the extract air fan, the non-return damper and the motorised shut-off damper before it is discharged to the outside as exhaust air. If the room air quality is sufficient, FSL-CONTROL III closes the outdoor air dampers and changes to secondary air operation, which is more energy efficient in any case. The control system compares the room air quality setpoint value to the actual value measured by the CO2 sensor and switches automatically between outdoor air and secondary air operation. If the power fails, the outdoor air and exhaust air dampers are closed to ensure fire protection and frost protection and to avoid draughts. This is ensured by a capacitor in each actuator. The supply air is discharged near the external wall and with a medium velocity between 1.0 and 1.5 m/s. Due to the induction effect, the supply air velocity is rapidly reduced so that, in cooling mode, the supply air displaces the room air over the entire floor area. The convection from people and other heat sources causes the outdoor air to rise and create comfortable conditions in the occupied zone.

Width1085 mm
Height630 mm
Depth320 mm
Outdoor air flow rate

80 – 150 m³/h

Nominal volume flow rate

120 m³/h


Sound power level

30 – 43 dB(A)

Heat recovery efficiency

60 %

Max. operating pressure, water side

6 bar

Max. operating temperature

75 °C
Supply voltage230 V AC ±10 %, 50/60 Hz
Power rating

234 VA


Weight

65 kg


 

RA-B-ZAB/SEK4HE
KR/1124 × 763 × 320 / C3 / MAT / MR / C / Z / A / HVR0.4 / KVR0.4
||||||||||||||||||
123456789101112131415161718
1 Type
RA-B-ZAB/SEK horizontal decentralised sill ventilation unit XCUBE/ROOMAIR-B-ZAB/SEK

2 Heat exchanger
2
2-pipe
4 4-pipe

3 Variant
No entry: Standard 
HE high degree of heat recovery

4 Construction
KR
 with condensate drain on the right

KL with condensate drain on the left (only with variant HE)

5 Dimensions [mm]
Width × height × depth

1085 × 630 × 320 (only with standard variant)
1124 × 763 × 320 (only with variant HE and version KR)

1174 × 763 × 320 (only with variant HE and version KL)

6 Control system
OR
without control system
C3 with FSL-CONTROL III

7 Control function
MA
Master
SL Slave

8 Real time clock
Only with control function MA
No entry: without real time clock
T with real time clock

9 Interface
No entry: without interface
MT with Modbus TCP
MR with Modbus RTU (only with control function MA)
BI with BACnet IP
BM with BACnet MS/TP (only with control function MA)

10 Air quality sensor
Only with control function MA
No entry: without air quality sensor
C with CO2-sensor
V with VOC sensor

11 Supply air temperature sensor
Z
with supply air temperature sensor

12 Outdoor air temperature sensor
Only with control function MA
No entry: without outdoor air temperature sensor
A with outdoor air temperature sensor

13 Heating valve
HV
with heating valve

14 Lockshield – heating circuit
R
with lockshield

15 kVS value – heating valve
0.25
Straight-way valve
0.40 Straight-way valve
0.63 Straight-way valve
1.00 Straight-way valve
F0.50 Pressure-independent control valve

16 Cooling valve
With heat exchanger '4' only
KV with cooling valve

17 Lockshield – cooling circuit
R
with lockshield

18 kVS value – cooling valve
0.25
Straight-way valve
0.40 Straight-way valve
0.63 Straight-way valve
1.00 Straight-way valve
F0.50 Pressure-independent control valve


Order example: FSL-B-ZAB/SEK-4-KM/1085x630x320/C3-MA-T/C/Z/A/HV-R-0.40/KV-R-0.25

FSL-B-ZAB/SEKHorizontal under sill unit
4With 4-pipe heat exchanger
KMWith condensate drain
C3With FSL-CONTROL III
MAMaster
TWith real time clock
CWith COsensor
ZWith supply air temperature sensor
AWith outdoor air temperature sensor
HV-R-0.40With straight-way valve (heating circuit) KVS 0.40 and lockshield
KV-R-0.25With straight-way valve (cooling circuit) KVS 0.25 and lockshield

 

Letöltések

termékinformáció

tanúsítványok

kezelési útmutatók

production {"x-frame-options"=>"SAMEORIGIN", "x-xss-protection"=>"0", "x-content-type-options"=>"nosniff", "x-permitted-cross-domain-policies"=>"none", "referrer-policy"=>"strict-origin-when-cross-origin", "strict-transport-security"=>"max-age=31536000; includeSubDomains", "content-type"=>"text/html; charset=utf-8", "link"=>"</assets/application-efbc495b06ca980ef13dc743756002fce2f413f798fecb64c7f0c81954c16402.css>; rel=preload; as=style; nopush,</assets/print-fec2e47d6d8dcc5d4c101139f17046ba981ca1c12f71e7e403fba50cc7584175.css>; rel=preload; as=style; nopush,</assets/other_js/modernizr.custom.93544-c26374a79d804901074bb4aa6fd3fa44ea22e840389915d2adce16b024021ef3.js>; rel=preload; as=script; nopush,</assets/other_js/js.cookie.min-de103d86d1919b40950f791699b4ce768137fde41af09b35ff92bde369732183.js>; rel=preload; as=script; nopush,</assets/other_js/jquery-3.5.1-2c4ce18a1a3f144c333912efc24a76c9a165a0dba9f88a499985df1af0a196a2.js>; rel=preload; as=script; nopush"}

Oldal megosztása

Oldal ajánlása

Oldal ajánlása, hivatkozás küldése e-mailben.

A *-gal jelölt mezők kitöltése kötelező.

Oldal megosztása

Köszönjük, hogy ajánlott minket!

Ajánlását elküldtük és hamarosan meg kell érkeznie.


Kapcsolat

Hol tartózkodik Ön?

Adja meg üzenetét és kérése típusát
Tel.: +36 (1)212-1211 | Fax: +36 (1)212-0735

Attachment (max. 10MB)

A *-gal jelölt mezők kitöltése kötelező.

Kapcsolat

Köszönjük üzenetét!

Az üzenet elküldve, hamarosan feldolgozzuk. Szervizigényekkel foglalkozó részlegünk a lehető leghamarabb felveszi Önnel a kapcsolatot.
Általános, termékekkel, szolgáltatásokkal kapcsolatos kérdéseivel a következő telefonszámokon is fordulhat hozzánk:
Tel.: +36 (1)212-1211 | Fax: +36 (1)212-0735

Kapcsolat

Hol tartózkodik Ön?

Adja meg üzenetét és kérése típusát
Tel.: +36 (1)212-1211 | Fax: +36 (1)212-0735

Attachment (max. 10MB)

A *-gal jelölt mezők kitöltése kötelező.

Kapcsolat

Köszönjük üzenetét!

Az üzenet elküldve, hamarosan feldolgozzuk. Szervizigényekkel foglalkozó részlegünk a lehető leghamarabb felveszi Önnel a kapcsolatot.
Általános, termékekkel, szolgáltatásokkal kapcsolatos kérdéseivel a következő telefonszámokon is fordulhat hozzánk:
Tel.: +36 (1)212-1211 | Fax: +36 (1)212-0735